Legend
- Gas inlet
- Gas outlet
- Pulse generator port (option)
- Removable cover
Performance Data
Minimum flow Qmin | 60 | ltr/h |
Standard flow Qstandard | 5,000 | ltr/h |
Maximum flow Qmax | 10,000 | ltr/h |
Measurement accuracy (2) | 2 | % |
Measuring cavity capacity | 3.5 | ltr/U |
Temperature range | -20 to +50 | °C |
Maximum gas inlet pressure | 300 | mbar |
Minimum differential pressure (1) | 1 | mbar |
Minimum dial division | 0.2 | ltr |
Indication dial plate | 20 | ltr |
Maximum indication value (3) | 99,999,999 | ltr |
Weight | 6.4 | kg |
- (1) Differential pressure (= pressure loss) gas inlet gas outlet
- (2) Across the measuring range in relation to the calibration value at nominal flow
- (3) Standard Totalizing Roller Counter
No reverse flow direction possible!
Models (materials)
- Casing: zinc-coated steel sheet (soldered) with outside also lacquered
- Measuring unit: Tinplate
- Bellows (within measuring unit): textile-reinforced nitrile rubber (Perbunan®)
- Rod linkage: Polyamide
- Slide gate: Bakelite
Standard Equipment
- Twin-Chamber Measuring Unit
- 8 or 9-digit Totalizing Roller Counter
- Large One-needle Dial
- Magnetic Coupling (between measuring drum and counting mechanism)
- Screw connection 1-1/4″ (G 1-1/4 A, DIN ISO 228)
Built-in Options
- LCD Display, resettable, 8-digit (replaces Totalizing Roller Counter)
- Pulse Generator, standard or Ex-proof version (for connecting Electronic Display Unit/Computer)
Accessories
- Thermometer (BG)
- Manometer for pressure pmax = 60 mbar
- EDU 32 FP, displays volume and calculates flow rate via RS232 and analog-output in realtime (pulse generator required)
- Nozzles for flexible tube connection
V 3.0 / Rev. 2024-07-03 / Subject to alterations.
The most recent version of this data-sheet can be found at …
https://www.ritter.de/en/data-sheets/bg-6/
Dr.-Ing. RITTER Apparatebau GmbH & Co. KG · Coloniastrasse 19-23 · D-44892 Bochum · Germany
For questions please contact mailbox@ritter.de or your local distribution partner (on our overview page)
https://www.ritter.de/en/data-sheets/bg-6/
Dr.-Ing. RITTER Apparatebau GmbH & Co. KG · Coloniastrasse 19-23 · D-44892 Bochum · Germany
For questions please contact mailbox@ritter.de or your local distribution partner (on our overview page)