Safety Valve – closed completion
| Suitable for: | RITTER drum-type and bellows-type gas meters |
| Gases: | toxic |
| Set pressure: | 50 mbar |
| Maximum flow rate: | Air (0°C) 11 Nm³/h |
| Material: | 1.4571 / 1.4581 |
| Function: | Spring loaded |
| Operating temperature: | -60°C to +280°C |
| Installation position: | vertical |
| Sealing: | Viton |
Caution:
If the pressure will exceed 50 mbar, the safety valve will open. However, if the flow rate from the gas source exceeds the above-mentioned max. flow rate, the valve would not be able to vent the meter quickly enough.
This would built-up a pressure inside of the meter and may destroy the gas meter despite of the opened valve!

Subject to alterations